    Boards Address when Adding a Device to Scada with ION Protocol

    Issue
    An Ethernet device is added to the project using ION protocol, however, the device does not communicate.

    Product Line
    PowerScada Expert 8.1 (PSE 8.1)

    Environment
    Citect Project Editor > Boards

    Cause
    The 'Address' field in the Boards form is set to 0 by default.  The address for an ION meter connected through Ethernet is 100 by default.

    Resolution
    In the Boards form, set the address to 100.  Pack, Compile and Run the project again.

              
     