    Can 755PSMA and 755SMA be interlinked with 755PSMA2?

    Yes 755PSMA and 755SMA can be interlinked / interconnected with 755PSMA2. Interconnecting smoke alarms is a method of joining a series of alarms so that if any one alarm senses smoke, all the connected alarms will operate (alarm).  A 9 V signal is applied to the interconnect wire (referenced to neutral) to alarm all the other interconnected alarms.
    • All interconnected smoke alarms must be supplied from the same circuit.
    • A common Neutral must be used for the Interconnect to operate.
    • DO NOT connect the Interconnect wire to Active or Neutral.
    • A maximum of 40 Clipsal 755 smoke alarms can be installed on one circuit (wired interconnection only).
    • Only Clipsal smoke alarms can be interconnected with each other.
    Failure to follow these instructions may result in injury and equipment damage / malfunction.