    How to enter Pump Curve Data on an Altivar 6xx Process Drive?

    Issue:
    How to enter Pump Curve Data on an Altivar 6xx Process Drive?

    Product Line:
    ATV6xx

    Environment:
    All models and serial numbers

    Cause:
    To monitor behavior of pump curve

    Resolution:
    ATV630 Process Drive Pump Curve Setup
     
    Prerequisites to entering Pump Curve Data 
    Initial Configuration
    • Motor Settings
    • Speed Control Settings
    Pump Curves
    • Enter pump characteristics & activate pump curves

    Initial Configuration

     
    Complete Settings => Motor Parameters + AutoTune (Also available in Simply Start Menu)
    Base Frequency (BFR)  = 60 Hz
    Motor Power (NPR) =
    Nominal Motor Speed (NSP) =
    Nominal Motor Current (NCR) =
    Motor Thermal Current (ITH) =
    Motor Control Type (CTT) =
    Auto Tune (TUN) =
     
    Complete Settings => Macro Config
    Application Selection (APPT) = General Pump Control
     
    Complete Settings => Define System Units
    P Sensor Unit (SUPR) = ft
    Flow Rate Unit (SUFR ) = GPM
    Temperature Unit (SUTP) = F
     
    Simply Start
    Low Speed LSP =
    High Speed HSP =
    Acceleration ACC =
    Deceleration DEC =

    Pump Curves

    Pump Characteristics curves entered
    Activate Curves
     
     

    Pump Characteristics (Data Sheet)

     

     
    Point Flow
    (GPM)
    Head
    (Ft)
     
    Head
    (psi)
    Power
    (HP)
    1 0 80.9   76.8
    2 2585 59.5   71
    3 4509 49.5   70.2
    4 6737.7 27.1   61
    5 7720 16   51.8
    BEP 5560 40.1   66.8
     
    The following pump curve settings can be made through the Keypad display, SoMove configuration software or the embedded web page.
    Complete Settings => Pump Characteristics
    Pump Curve Mode (PCM) = PHQ
    Pump Speed (PCSP) = 1190
    Flow 1 (PCQ1) = 0
    Flow 2 (PCQ2) = 2585
    Flow 3 (PCQ3) = 4509
    Flow 4 (PCQ4)  = 6737.7
    Flow 5 (PCQ5) = 7720
    Flow BEP (PCBQ) = 5560
    Head 1 (PCH1) = 80.9
    Head 2 (PCH2) = 59.5
    Head 3 (PCH3) = 49.5
    Head 4 (PCH4) = 27.1
    Head 5 (PCH5) = 16
    Head BEP (PCBH) = 40.1
    Power 1 (PCP1 = 76.8
    Power 2 (PCP2) = 71
    Power 3 (PCP3) = 70.2
    Power 4 (PCP4) = 61
    Power 5 (PCP5) = 51.8
    Power BEP (PCBP) = 66.8
    Pump Curve Activate (PCA) = YES