    Why will the 8839 E-Flex not start in auto mode?

    Issue:
    Why will the 8839 E-Flex not start in auto mode?

    Product Line:
    8839 EFD  E-Flex enclosed drives

    Environment:
    All

    Cause:
    ​The drive runs in hand and bypass not in auto mode? 

    Resolution: 
    Verify the auto start contact is closed between terminals 7 and 6.
    Verify 120Vac  at the RCR relay pin 6.
    Verify the drive is not in a fault state.