    S-Flex (ATV212) ramping motor up to 60 Hz, not following analog input.

    Issue:
    S-Flex (ATV212)  ramping motor up to 60 Hz, not following analog input.

    Product Line:
    S-Flex enclosed drive
    ATV212, Altivar 212
    ATV21, Altivar 21

    Environment:
    All part numbers, all models

    Cause:
    Not operating as expected

    Resolution:
    1) Verified FnOd is set properly (1 for VIA, 2 for VIB, 3 for HMI, 4 for Serial Communication).
    2) Check logic input programming to be sure a preset speed command is not present (F108, F110, F111, F112, F113)
    3) Make sure F360 (PID Control enable) is set to 0 if not using PID in the drive.
    4) If using PID control, check feedback signal and setpoint.

    Consult ATV212 programming manual for details.
    Found F360 was set to 1 so the drive was in PID mode but had no feedback signal.
    Turned F360 to 0 and the drive operated properly.