    What are the causes and remedy for Err8 fault on the ATV212 or SFD212 drives?

    Issue:
    What are the causes and remedy for Err8 fault on the ATV212 or SFD212 drives?

    Product Line:
    Altivar ATV21, ATV212 SFD21 and SFD212 drives

    Environment:
    All 

    Cause:
    Loss of network or network timeout has occurred.

    Resolution:
    Err8 means network communication fault error. Try checking the network control devices and cables.
    The function can be disabled temporarily for troubleshooting by setting F803 to 0 and F851 to 1. However, please do not leave the network disabled. Once troubleshooting is over, please enable F803 back to 1 and F851 back to 4.