    Change Location

    What will cause an LRF fault on the ATS48 soft starters?

    Issue:
    What will cause an LRF fault on the ATS48 soft starters?

    Product Line:
    Altistart ATS48 soft starters

    Environment:
    All

    Cause:
    Locked motor rotor. 

    Resolution:
    Locked rotor in steady state
    This fault is only active in steady state with soft starter bypass
    contactor. It is detected if the current in a phase is greater than
    or equal to 5 IN for more than 0.2 s.
    Check the mechanism for wear, mechanical play, lubrication, blockages,
     