    Why is my drive not storing parameter changes after a power cycle.

    Issue:
    Parameter changes made to the drive over a network (ModBus, CANopen, etc)  reset to default values after a power cycle.

    Product Line:
    ATV31, ATV312, ATV12, ATV61, ATV71

    Environment:
    All part numbers.
    Adjusments via network

    Cause:
    Parameter changes are made to RAM and not to EEPROM

    Resolution:
    Adjustments made over the network are stored to the operating memory (RAM) in the drive so it will be lost after a power cycle.
    To have the settings stored to the EEPROM the customer must set Bit 1 of the CMI (Extended control word; address 8504) to 1.
    This bit will reset to 0 after a save had been completed.

    NOTE: The EEPROM has a limit to the number of times it can be written.  This is 1,000,000 writes for the ATV312.  ATV12, ATV61 and ATV71 are limited to 100,000 writes