    How to calculate counter frequency in Scadapack3xx?

    Using Flow block in Telepace Studio Software:
    Frequency = Flow rate/K factor
    Example:

    set K factor =1;
    use Counter CH0 register = 30009;
    Input type = 32 bit counter;
    Rate period = Per second;

    To get the flow rate in the Flow block:
    Flow rate status and data block register +1 and +2 = flow rate (floating-point). These registers contain the flow rate in engineering units based on the K-factor and rate period provided (same for every flow rate register.)

    Since the K factor is equal to 1.
    Therefore:
    Frequecy = Flow rate