    Vista diagram displaying incorrect phase link and label for ION6200 two-wire mode

    Issue
    The default diagram for the 2-wire mode ION6200 meter is linked an labeled incorrectly for the a-Phase kW.

    The diagram displays "kW c" instead of "kW a" and the associated numeric register is linked to the "kW c" register on the meter.




    Product Line
    ION6200
    Power Monitoring Expert 7.2.x/8.0
    StruxureWare Power Monitoring 7.0.x
    ION Enterprise 6.0.x

    Environment
    Vista and Web Applications Diagrams

    Resolution
    The attached ".dgm" file should be placed in the following directory to replace the original.

    "...\config\diagrams\ud\default\6200_FAC-2WYE_V1.3.1"




     