    Video: How can the type of stop be changed for the ATV312 (or ATV31) drive?

    Issue:
    Need to change the Stop Type on the ATV312 drive.

    Product line:
    ATV312, Altivar 312, ATV31

    Resolution:
    The default setting for Type of Stop on the ATV312 drives is Ramp stop.

    The options for stopping are:

    • Ramp
    • Freewheel
    • Fast Stop
    • DC Injection. 

    Programming below is showing the drive code and in brackets, (text using the VW3A1101 remote HMI display)
    To access the Stop Mode, go to the FUn- (Application function) menu, then StC- (Stop Mode) then Stt (Type of stop).  The options are:
    - rNP (Ramp)
    - FSt (Fast stop)
    - nSt (Freewheel)
    - dCI (DC Injection)

    Please note that nSt (Freewheel), FSt (Fast stop) and dCI (DC Injection) can also be assigned to other logic inputs under the StC- (Stop Modes) menu.
     