    How do you set up the damper control on the enclosed S-Flex ATV212 drive?

    Issue:
    How do you set up the damper control on the enclosed S-Flex ATV212 drive?

    Product Line:
    S-Flex ATV212 with bypass 

    Environment:
    All 

    Cause:
    Wants to wire in a damper control circuit to allow the damper to open before running the motor thru the drive. 

    Resolution:
    Step #1 Customer commands the drive to run by closing terminals (5-6) auto start. (Drive will not start at this time or until damper is opened)

    Step #2 Closing the auto start terminals  (5-6) will energize the RPR relay which will close user contacts (19-20) to start damper solenoid coil.

    Step #3 Damper solenoid will start to open damper.

    Step# 4 Once the damper is open the customer will need to provide a end of damper feedback limit switch. 

    Step #5 Remove the jumper from terminals (3-4) and wire your end of damper feedback dry NO contact to terminal (3-4).

    Please note that this damper function will only work in the remote control mode by closing contacts (5-6) and not the local mode run button on the face of the drive. 