    How is the S-Flex wired to use or not use the Smoke Purge feature?

    Issue:
    How is the S-Flex wired to use or not use the Smoke Purge feature?

    Product Line:
    S-Flex

    Environment:
    S-Flex with Bypass option

    Cause:
    Wiring to enable or disable smoke purge

    Resolution:
    All S-Flex Series E units that have the BYPASS option will also have a SMOKE PURGE feature, although it is disabled.  To enable the smoke purge function, simply remove the jumper from terminals 3-4 and place it on terminals 9-10.  This feature includes a smoke purge relay, SPR, that is activated by applying 120Vac across terminals 17-18.  When activated, SPR contacts will disable the AFC / BYP controls and energize the bypass contactor coil.  The motor will run with full voltage AC power.


     