    Can an analog input be used for the PID reference with the Altivar Process drive?

    Issue:
    Can an analog input be used for the PID reference with the Altivar Process drive?

    Product Line:
    ATV 600/900 series

    Environment:
    All models, All serial numbers

    Cause:
    Customer has an application with a dynamic setpoint and needs to use 4-20ma input for the PID reference.

    Resolution:
    Yes, If parameter PII (Internal PID Reference) is set to NO, the drive will use the Reference 1 channel as the PID reference.  Reference 1 channel can be configured for any analog input.