    Conext SW torque specifications for DC and AC switchgears

    Issue:
    Torque requirements for wiring a CSW system.

    Environment:
    Conext SW AC Switchgear and DC Switchgear

    Cause:
    The torque specifications for the AC and DC switchgear are not readily apparent in the installation guide for either product or the CSW.  There is a sticker on the interior of these products detailing torque.

    Resolution:

    For the connections for the battery terminals of the CSW inverter:

    Make sure the supplied nuts on the inverter/charger are tightened to a torque of 10–11 ft-lbs (13.5–14.9 Nm). Torque all other connections to the manufacturer’s specifications.

    For all other connections:
    Tightening Torque
    Wire Gauge in*lb mm2 N*m
    14 - 10 35 2.08 - 5.26 4.0
    8 40 8.36 4.5
    6 - 4 45 13.29 - 21.14 5.1
    3 - 2/0 50 26.65 - 67.40 5.6