    Error in MiCOM S1 Studio Not Supported when using quick connect.

    Issue
    When trying use the quick connect in MiCOM S1 Studio a Not Supported error appears beside the data model number. 


    Product Line  
    MiCOM S1 Studio

    Environment     
    Connecting to MiCOM relays

    Cause    
    The MiCOM data model that is being connected to is not on the computer that is being used.

    Resolution    
    The first step will be to download the data model from Data Model Manager.  The instructions are in the follow article FA221295
    Once the data model is download try the quick connect again.   The model will now not have the not supported error.

    Note: That if a password is asked for the default is AAAA password unless changed in MiCOM S1 Studio

     