    On the ATV61 and ATV71 drives how can you add another run permissive input if you already have freewheel stop assigned?

    Issue:
    On the ATV61 and ATV71 drives how can you add another run permissive input if you already have freewheel stop assigned?

    Product Line:
    ATV61/71

    Environment:
    All serial numbers for ATV61/71

    Cause:
    N/A

    Resolution:
    There are several options of adding another run permissive on this drive.
    - You can remove the factory jumper and tie in your stop circuit between the PWR and +24 terminals
    - You can assign a Fast Stop as a logic input
      - Drive Menu ~> 1.7 Application Function Menu ~> Stop Configuration ~> Fast Stop Assignment
    - You can use an External Fault with either Normally Closed or Normally Open set of contacts
      - Drive Menu ~> 1.8 Fault Management Menu ~> External Fault ~> External Fault Assignment



     