    How do you set up a run permissive on the S-Flex enclosed or ATV212 drives?

    Issue:
    How do you set up a run permissive on the S-Flex enclosed or ATV212 drives? 

    Product Line:
    Altivar ATV212 and S-Flex enclosed

    Environment:
    All

    Cause:
    The ATV212 drive is not shutting down when they open the permissive input on R.

    Resolution:
    Check the programming
    Find F------ codes enter
    Find F100= this needs to be set to 0
    Find F112= this if the R input assigned as the permissive. Set this to 1
    Now when you open the R digital input the drive will shut down and display OFF.

    For S-flex units.  Terminals 1 and 2, 2 and 3, and 3 and 4 have jumper from the factory that are normally used for damper end switch or fire/freeze stat inputs.
    If any one of those are not being utilized, you can remove the jumper from one of those inputs and tie your safety (permissive) wires accordingly.
     