    Can you connect 24vdc or 120vac to the start terminals 5-6 on the S-flex enclosed drive?

    Issue:
    Can you connect 24vdc or 120vac to the start terminals 5-6 on the S-flex enclosed drive?

    Product Line:
    Altivar ATV21 or ATV212 S-flex enclosed

    Environment:
    All

    Cause:
    They have a start command with voltage and want to know if they can put it on the start terminals 5-6.

    Resolution:
    We only recommend that you put a dry contact between terminals 5-6 for the start command.  We are supplying the 120vac power to these terminals.  Please do not bring your own voltage into there terminals.