    ETSNZ - What indication contact options are available for Masterpact ACBs?

    Standard or low-level contacts:

    ON/OFF indication (OF)

    “Fault trip” indication (SDE)

    Carriage switches for
    Connected - changeover contacts to indicate the “connected” position CE
    Disconnected - changeover contacts to indicate the “disconnected” position CD. This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached
    Test - changeover contacts to indicate the “test” position CT. In this position, the power circuits are disconnected and the auxiliary circuits are connected.

    Programmable contacts:

    2 contacts (M2C)

    6 contacts (M6C)

    These contacts, used with the Micrologic E, P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option.
    They require an external power supply module. The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used to signal threshold overruns or status changes.
    They can be programmed using the keypad on the Micrologic P control unit or remotely using the COM option (BCM ULP).