    ETSNZ - What is the difference between BD and BL 24VDC control in the Tesys Contactor LC1D09-38 range?

    Both are 24VDC control, the BL is a low consumption coil for operation with a low-level DC signal without the need for an interposing relay.
    The average consumption of the BD coil is 5.4W inrush and sealed.
    The average consumption of the BL coil is 2.4W inrush and sealed.
    The low consumption BL coil limits the auxiliary contacts that can be fitted to the contactor.
    Attached document shows complete charactistics of both coil types and the maximum number of auxiliary contact blocks that can be fitted.