    How can an ATV212 drive be setup to ignore a com fault and continue running at same speed before the fault?

    Issue:
    How can the drive be setup to ignore a com fault and continue running at same speed before the fault? 

    Product Line:
    ALTIVAR 212

    Environment:
    All

    Cause:
    Ride through functionality in case of communications faults.

    Resolution:
    Set parameter F851 under AUF, F--- to value 1 for no active.  This will ensure that if the drive is running at a specific speed before fault it will continue to run at the same speed even after com fault occurs. 
     