    What can cause an CFF fault on the ATV12 drives?

    Issue:
    What can cause an CFF fault  on the ATV12 drives?

    Product Line:
    Altivar ATV12

    Environment:
    All

    Cause:
    Drive is powering up with an CFF fault and will not clear.

    Resolution:
    CFF= incorrect configuration fault.

    Possible causes:
    -HMI block replaced by and HMI block configuration on a drive with a different HP ratings.
    -The current parameter of the customers parameter is inconsistent.

    Remedy:  Try resetting the drive back to a factory default by going into the
    ConF  menu enter
    FCS menu enter
    change FCS menu to InI and hold for 2 seconds.
    Now power cycle the drive.
    If the fault clears now try and reprogram the drive.  If you are still getting the CFF fault you will need to replace the drive.