    How to deal with HMIG5U Runtime Error:"Secondary storage device is missing or does not have enough space. Run-time operations that require this storage device will fail".?

    For HMIG5U, the secondary storage is SD card or CFast card.
    There are too possible reasons for above error message:
    1. The SD card or CFast card is full. use Data Manager to extract and delete the data from target machine;
    2. The SD card or CFast card is missing, or the Drive Label is incorrect. i.e. Drive E:\ has been specified as Secondary Drive under Data Locations. However, Windows assisgned a different Label,i.e. D:\ to SD or CFast cards.
    3. If the issue still there, replace the SD card or CFast Card. Try the Runtime Installer. Then redownload the project.