    TCSEGPA23F14F Profibus Remote Master (PRM) modules experiencing System Fault (SF) during RUN.

    Goals and Symptoms
     
    TCSEGPA23F14F Profibus Remote Master (PRM) modules experiencing System Fault (SF) during RUN.
     
     
    Facts and Changes
     
    PRM modules experiencing SF failures in operation and commissioning. SF LED is on Steady module will not go back into RUN.
     
    Causes and Fixes
     
    An issue was discovered with the Firmware that led to this fault. It was corrected in Version 1.0.24.4 of the firmware.
     
    There is considerable confusion regarding the identification of the firmware of the PRM. The only way to identify the current version is to use the DTM Browser in UnityPro to connect online to the PRM and read the version directly from the unit via the Device Menu->Diagnostics. If found to be earlier than 1.0.24.4, it should be updated
     
    The update is performed using the DTM Browser but some preparation may be  needed. The file needs to be renamed "PRMOS.bin" if not already done. No exceptions.
     
    Using the DTM Browser:
     
    1. Right Click on the Instance and select Device Menu ->Download Firmware.
     
    Note that the PRM will reboot at the end of the transfer.
     
     
    1. After the Reboot confirm the version has changed using the Diagnostic function.
     
     
     
    Additional Information
     
     The firmware and additional information found in this document are part of the Profibus Remote Master V1.2 CD. The firmware is found in the Firmware directory on the CD