    Can the logic be inversed on a logic input assigned as an external fault on the ATV61 and ATV71 drives?

    Issue:
    Can the logic be inversed on a logic input assigned as an external fault on the ATV61 and ATV71 drives?

    Product Line:
    ATV61/71

    Environment:
    All models

    Cause:
    N/A

    Resolution:
    Yes.  After setting an External Fault assignment to a logic input, the External fault config (LEt) determines the IO logic. 
    If LEt = Active high, then the fault is triggered as the LI transitions from low to high.
    If LEt = Active low, then the fault is triggered as the LI transitions from high to low.