    What can cause and GrdF ground fault on the ATS22 soft starter?

    Issue:
    What can cause the ATS22 softstart unit to trip on Ground Fault (GrdF)?

    Product Line:
    ATS22


    Environment:
    All

    Cause:
    Tripping the unit

    Resolution:
    This is a Ground Leakage current detected fault.
    Check the motor and wires insulation.
    Check for proper installation and Grounding.
    Check the settings Grdd, Grdt parameters in PrO menu.