    Video: Total Power Off Procedure for All Single Phase Symmetra Units

    Issue
    Proper procedure for powering down a single phase Symmetra

    Product Line
    Symmetra LX, Symmetra RM, Symmetra Power Array

    Environment
    All Single Phase Symmetra

    Cause/Overview
    There are times when it may be required to power down the Symmetra. Such instances could be to change out a system fan depending on the type of Symmetra, or changing out a backplate.

    Resolution
    The total power off procedure for Symmetra systems are found on the back of all of the systems.
    The procedure is as follows:

    1. Set the System enable Switch to Standby
    2. Set the Input Circuit Breaker to Standby
    3. Disconnect the Battery Modules
    4. Disconnect external Battery Cabinet (if provided)
    5. Disconnect Mains/Branch Circuit


     

     