    How can I simulate a fault condition on my ATS22 or ATS48 soft starter to verify my fault status circuitry connected to the starter is working properly?

    Issue:
    How can I simulate a fault condition on my ATS22 or ATS48 soft starter to verify my fault status circuitry connected to the starter is working properly?

    Product line:
    ATS22 and ATS48 series soft starters

    Environment:
    All models, All serial numbers

    Cause:
    Customer needs to generate a fault condition on the starter in order to verity their building management system registers the fault properly.

    Resolution:
    An easy way to generate a fault on an ATS22 or ATS48 series starter is to provide a run command to the starter when the motor is not connected.  The ATS22 will display SCCR and the ATS48 will display PHF.  Any relays assigned to a fault function will actuate.