    What can cause an Err5 fault on the S-Flex ATV212 drives?

    Issue:
    What can cause an Err5 fault on the S-Flex ATV212 drives?

    Product Line:
    Altivar ATV212  S-Flex

    Environment:
    All with an serial coms setting turned on.

    Cause:
    Started to get the Err5 fault after setting F829 to Lowworks control

    Resolution:
    Err5 is a serial communications error.  If you program F829 to be controlled over the network, make sure you are sending a signal within the programmed timeout period.
    Check timeout setting on F803.
    Check the remote HMI cable if they used.
    Check the F829 settings, try setting F829 back to 1 and cylce power to see if it will clear the Err5.
    If the Err5 fault is cleared, set F829 back to 5 for Lonworks communication. 

     