    Power cycled the HMISCU and getting the message: "the codesys runtime has stopped". How to put the controller into Run?

    Issue:
    Power cycled the HMISCU and getting the message: "the codesys runtime has stopped".  How to put the controller into Run?

    Product Line:
    HMISCU, Somachine

    Environment:


    Cause:


    Resolution:
    There is no Run input for the HMISCU combo units.  You will need to create an external variable with an address of @Prop:0 in Vijeo Designer.  Then create an Action on start up to write a value of "1" to that external variable.