    What does WRITE_REG error 6007 indicate when used in a Quantum over Ethernet TCPIP.

    This means that the NOE module slot mapping register is set incorrectly.
     
    The ADDRFLD pin is an Array of 5 words. The high byte of the first word is the physical slot position in HEX of the Ethernet module. The low byte is the Modbus mapping index if going through a bridge. A setting or 0500 HEX would mean that the NOE that the message is going out on resides in slot 5 and no index is needed for the slave device.
    The remaining 4 words are the IP address of the slave device.