    What can cause an SCF4 fault on the Altivar ATV12 drives?

    Issue:
    What can cause an SCF4 fault on the Altivar ATV12 drives?

    Product Line:
    Altivar ATV12

    Environment:
    All

    Cause:
    ATV12 drive is powering up with an SCF4 fault.

    Resolution:
    SCF4 means IGBT short circuit fault.
    Possible issues: Internal power component short circuit detected at power on.  The drive may need to be replaced if the fault is coming up on power up. Check for any exploded/burnt electrical components on the drive. Also try running the drive without the motor leads connected and see if the fault persists. 

    A static check can be performed on the drive:

    Checking The Input and Output Diode Bridges
    This test is done using a digital multi-meter in diode test mode to check that the transistors and diodes are not short-circuited. 


    ALL TESTS ARE TO BE PERFORMED WITH ALL SOURCES OF POWER REMOVED FROM THE DRIVE

    For Altivar Drive up to 25hp
    • Instrument
      • Use Digit-Meter with a diode scale
    • Measurement
      • ​Locate PA+ and PC- input on drive power terminals (should be close to your power connection terminals)
      • Set meter to diode scale
      • To measure Input diodes
        • Place black on positive bus (PA+) and red on L1
        • Get readings and then move to L2 and then L3 
        • When done swap red and black probes and measure again between (PA+) to L1...L3
        • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)
      • To measure Output diodes
        • Place black on positive bus (PA+) and red on T1
        • Get readings and then move to T2 and then T3 
        • When done swap red and black probes and measure again between (PA+) to T1...T3
        • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)

    For Altivar Drive over 25hp
    • Drive uses SCRs on the positive input bridge and diodes on the negative. For the Output Bridge its all diodes.
    • Instrument
      • Use Digit-Meter with an ohm and a diode scale
    • Measurement
      • ​Locate PA+ and PC- input on drive power terminals (should be close to your power connection terminals)
      • To measure Input SCRs and diodes.
        • Set meter to ohm scale
        • Place black on positive bus (PA+) and red on L1
        • Get readings and then move to L2 and then L3 
        • When done swap red and black probes and measure again between (PA+) to L1...L3
        • Readings should be at least 50kohms.
        • Set meter to diode scale
        • Place black on positive bus (PC-) and red on L1
        • Get readings and then move to L2 and then L3 
        • When done swap red and black probes and measure again between (PC-) to L1...L3
        • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)
      • To measure Output diodes
        • Place black on positive bus (PA+) and red on T1
        • Get readings and then move to T2 and then T3 
        • When done swap red and black probes and measure again between (PA+) to T1...T3
        • Readings should be OL in one direction and a low voltage reading the other way (Example 0.3v)

    Didn’t find what you were looking for?