    What is the AL05 code shown on the ATV212?

    Issue:
    What is the AL05 code shown on the ATV212?
     
    Product Line:
    ALTIVAR 212, ATV212

    Environment:
    All
     
    Cause:
    Troubleshooting
     
    Resolution:
    AL05 is the alarm code display in case of a signal loss on an analog input.
     
    Example on VIA in 4-20mA
    FMOD = VIA
    [4-20 mA loss] F644 = freewheel
    [Loss of VIA] F633 = 20% --> 20% on F633 is for 4mA. 

    Start the drive with VIA higher than 4mA
       --> The drive run and goes to the speed given by VIA.
    If VIA signal is loose (VIA less than 4mA)
       --> AL05 is display showing the 4-20mA loss is detected.
       --> Then Drive is stopped in freewheel

    If AL05 is display on your product : 
       - check the signal level on VIA
       - then check F633 is set correctly

    There is nothing in manual on this code.