    How is a faulted ATS22 reset?

    Issue:
    How is the fault code cleared?

    Product Line:
    Altistart 22

    Environment:
    All models

    Cause:
    The fault code must be cleared to make ATS22 functional.

    Resolution:
    After the condition that created the fault has been corrected, a fault reset can be accomplished several ways:

    1) Remove control power from CL1-CL2. After the display has gone blank, apply control power.
    2) On the integral or remote keypad, press the 3-key combination of ENT / UP arrow / DOWN arrow, simultaneously.
    3) Wire a reset contact to logic input LI2 or LI3 and program it to rSt (remote reset). A momentary contact closure will reset.
    4) Use Modbus command word 752 and write a 1 to bit 3