    Is there a phase rotation parameter on the ATV312?

    Issue:
    Is there a phase rotation parameter on the ATV312? 

    Product Line:
    ATV312

    Environment:
    All serial numbers for ATV312 Drives

    Cause:
    Run forward command results in motor running in reverse rotation.

    Resolution:
    No, the ATV312 does not have a phase rotation parameter.  Typically, correction of rotation is accomplished by swapping 2 motor leads at the VFD output, T1/T2/T3.
    In the CtL menu, there is a Rotating Direction parameter, 'rot', that applies to the the remote keypad FWD/REV button only, when the command channel is LCC and speed reference channel is AIU1 or LCC.
    Information about 'rot' can be found on page 61 of the attached ATV312 Programming Manual. 