    What is the fuse size for the ATS22 CL1 CL2 control circuit?

    Issue:
    What is the fuse size needed to protect CL1-CL2 on the ATS22 soft starts? 

    Product line:
    ATS22, Altistart 22

    Environment:
    All models (S6 and S6U)

    Cause:
    The drawings and installation show fuse/overcurrent protection on CL1, but no notes on what size or type of protection to use.

    Resolution:
    According to our L3 team,  The CL1 - CL2 control voltage input should have a 1A fact acting fuse, or 1A circuit breaker for each ATS22 unit.  This applies to the 120 V and 230 V control supplies (Q, S6 and S6U)



     