    What's tha max Modbus TCP client and server connection number for M258 Ethernet?

    For the M258 & LMC058 controller, the Ethernet limitation connections are :

        SoMachine Protocol  : Maximum connection number = 4 (1)
        Modbus Server connection : Maximum connection = 8
        Modbus Client : : Maximum connection = 8
        Modbus Device : Maximum connection = 2
        Ethernet IP  Device : Maximum connection = 16
        FTP Server : Maximum connection = 4
        Web Server : Maximum connection = 10

    Theses ressources are independant between them (no link limitation connections between them)

    (1) The maximum number of SoMachine Protocol is 4.
    These connections can be :
        One connection for the HMI
        One for the OPC Server
        One for the SoMachine software
        One for the Trace object (oscilloscope function)