    What are the basic wiring connections for the ATV212 drive?

    Issue:
    What are the basic wiring connections for the ATV212 drive?

    Product line:
    ATV212, Altivar 212

    Environment:
    All models

    Cause:
    Limited wiring details provided with the drive.

    Resolution:
    The minimum requirements to operate an ATV212 drive are a run command and a speed reference.  By default from the factory, terminals F to P24 are the run forward and run permissive input.  VIA to CC is the default speed reference for 0-10V. 

    P24 has its own 24VDC power supply, so use a dry contact closure on F to P24. 

    **Note these values and assignments can be changed in the Programming.  These are the default settings only, with CNOd = 0 and FNOd = 1.