    How do you size a full voltage bypass contactor for the open type ATS48 soft starters?

    Issue:
    How do you size a full voltage bypass contactor for the open type ATS48 soft starters?

    Product Line:
    Altistart ATS48

    Environment:
    All

    Cause:
    Needs to add a full voltage bypass contactor to an open type ATS48 soft starter.

    Resolution:
    You will size the full voltage bypass contact to the size of the motor amps.   Please note that if you field install a bypass contactor you may need to add a line isolation contactor and add NC contacts so that you can turn off the soft starters control CL1 CL2 control voltage when you are in full voltage bypass.