    ATV61 ATV71 on a motor with PTC Probe.

    Issue
    ATV61 ATV71 on a motor with PTC Probe.

    Product Line:  
    ATV61, ATV71

    Environment
    All

    Cause
    PTC Probe connected but not working.

    Resolution:
    LI6 is a discrete input with which you can switch between two modes: PTC probe and 24V DC, in this case, the switch "SW2" has to be adjusted to "PTC" .
    Thermal monitoring via PTC probes is provided on ATV61 drives by specific inputs. Common characteristics of these inputs Nominal value < 1.5 kohms.  This corresponds to a maximum of 6 probes (250 ohms at 20°C) or to two sets of 3 (sometimes prewired in the motors).
    Trip resistance: 3 kohms. Reset value: 1.8 kohms. Short-circuit protection < 50 ohms
    Location of the inputs:
      - Input LI6 on the terminal block, wire the PTC probes between terminals LI6 and 0V; this input is seen as a PTC Input if switch SW2 at top of Control Terminal Card is set to PTC.
    Note: The parameter Overload Fault Mgmt MUST be set to something other than NO. You need to set it to freewheel.