Discover our Clipsal Smart Home packages as seen on The Block 2018

in location

OR

I'm looking for

  • Wholesalers
    • Uncheck All Check All
  • EXPERTISE
    • Expand
    • Expand
    • Expand
    • Uncheck All Check All
  • Switchboard Manufacturers
    • Uncheck All Check All
OR

The best way to see what Clipsal electric products can do for your home is seeing them in action at a Clipsal Display Centre.

Product stock may vary according to location. If you're after a specific product range, please check with your chosen location before visiting.

10 Results
    Load More Load Complete
    Change Location

    Why does the Enclosed ATS48 not come with power fuses?

    Issue:
    Why does the Enclosed ATS48 not come with power fuses?

    Product Line:
    Enclosed ATS48

    Environment:
    Models with fusible disconnect

    Cause:
    There is no power fuses in the Enclosed ATS48.

    Resolution:
    Units supplied with fusible switch disconnects require the user to supply and install the power fuses based on the power circuit and load.
    All of the Enclosed 48 controllers accept either UL Class J or L fuses, depending on the full load current rating.

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance