    What will cause the ATV212 drive not to start when the run contact between P24-F is closed?

    Issue:
    What will cause the ATV212 drive not to start when the run contact between P24-F is closed?

    Product Line:
    Altivar ATV21 and ATV212

    Environment:
    All

    Cause:
    When closing the run contact to logic input F, the VFD displays 0.0Hz.

    Resolution:
    - Verify that CMOd is set to 0 for terminal control.
    - If any network functions are enabled for monitoring purposes, set F108 = 48.
    - Check your logic input programming.  Typically F111 = 2 for run forward function.  Other possibilities may combine run forward with other functions.
    - Verify that the VFD is in Remote Mode.  The keypad LOC/REM button green LED should be OFF. 
    - Verify the VFD 24Vdc power supply by measuring P24 - CC.
    - Check that the run circuit is complete by measuring for 24Vdc on F - CC.
    - Verify that the VFD has a speed reference.  It may be running at 0Hz, indicated by a red RUN LED in the display.

     