in location

OR

I'm looking for

  • Wholesalers
    • Uncheck All Check All
  • EXPERTISE
    • Expand
    • Expand
    • Expand
    • Uncheck All Check All
  • Switchboard Manufacturers
    • Uncheck All Check All
OR

The best way to see what Clipsal electric products can do for your home is seeing them in action at a Clipsal Display Centre.

Product stock may vary according to location. If you're after a specific product range, please check with your chosen location before visiting.

10 Results
    Load More Load Complete
    Change Location

    What is the total distortion of ATS48?

    Schneider Electric does not have measured values of harmonics produced by softstarters.

    Softstarters conform to the following norm:
    IEC 60947-4-2: Low-voltage switchgear and controlgear - Contactors and motor-starters - AC semiconductor motor controllers and starters,
    which states, concerning harmonics:

    "8.3.2.1.1 Harmonics
    Subclause 7.3.3.2.2 of IEC 60947-1:2007 applies with the following addition:
    Because no significant harmonic emissions are produced in the FULL-ON state, tests are not
    required on those controllers or starters which run only in the FULL-ON state or which are
    by-passed by a mechanical switching device after completing a start, for example, Forms 2
    and 3 and certain Form 1 controllers or starters.

    8.3.3.6 Harmonics and commutation notches
    The test values and procedures are given in 9.3.5.2.5.

    9.3.5.2.5 Harmonics and commutation notches
    No requirement, the test levels are under study for the future."

    So, no special considerations or filtering are required for soft start applications.

    This is the reason why we do not make tests for that.

    Anyway, in the past some calculations were done to estimate it.
    ATS48 generates significant current harmonics only during the acceleration/deceleration phase, in steady state (when the thyristors are full conducting) they are negligible THD<2% and 0% with the starter bypassed.
    The harmonics level is difficult to calculate accurately because depends on the impedance of the all installation and it varies with the motor load (power factor is not constant).

    The following maximum values, are typical for a general case (during ACC/DEC only):
    Row 5 : 20% of fundamental
    Row 7 : 14% of fundamental
    Row 11 : 9% of fundamental
    Row 13 : 6.7% of fundamental
    Higher rows are practically negligible.

    Some tests were done for Row 3, unfortunately not for nominal load : less than 10% can appears with a low power factor.

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance