    Can the time duration be defined for a current limit status in an ATV71?

    Issue:
    Can the  torque limitation and current limitation ride through times be adjusted?

    Product Line:
    ATV71 ATV61

    Environment:
    All

    Cause:
    Need to delay current limit before the drive trips on fault.

    Resolution:
    Yes, the VFD can be configured for an action when status goes to CLI, current limitation, and after a time delay.
    Goto menu 1.8 FAULT MANAGEMENT (FLt)
    Goto submenu TORQUE OR I LIM. DETECT (tid-)
    Select parameter Trq/I limit. stop (SSb) and set to the desired behavior in the event of switching to torque or current limitation.
    Select parameter Trq/I limit. time out (Sto) and set the time delay for taking SSF "Limitation" fault into account.