    Why does the drive says "rdy" after the run command is given to LI1 on ATV312 drive?

    Issue:
    Why does the drive says "rdy" after the run command is given to LI1?

    Product Line:
    ATV312

    Environment:
    All

    Cause:
    Will not turn on motor

    Resolution:
    "rdy " on the HMI display means no run command has been issued.
    Measure voltage between LI1 and com terminals verify +24Vdc is present with run command
    Check the wiring between LI1 and +24Vdc ( customer switch )
    Verify the programming is setup for terminal control ( CCS and Cd1 menu CtL)
    Verify tCC settings for 2wire / 3wire matches the run command wiring. 
    Verify the drive is "not" in local mode ( push the green run button on the HMI )