    What is the tbS setting and status on an ATS48 soft start?

    Issue:
    What is the tbS setting and status on an ATS48 soft start?

    Product Line:
    ATS48

    Environment:
    All models and serial numbers

    Cause:
    N/A

    Resolution:
    This parameter avoids starts in quick succession which may overheat the motor. The time delay starts when the motor changes to freewheel mode. 
    In 2-wire control, the motor is restarted after the time delay if the RUN command input is
    still activated. 
    In 3-wire control, the motor is restarted after the time delay if a new RUN command is sent (rising edge).
    The soft starter displays "tbS" during the time delay.

    If tbS displays unexpectedly, check the run circuit.