    What is the Maximum wire size that will fit through the current transformers of the Branch Circuit Monitor (BCM)?

    Issue
    What is the Maximum wire size that will fit through the current transformers of the  Branch Circuit Monitor (BCM)?

    Product Line
    BCM
    BCMSC
    BCM42H
    BCM42Y55

    Environment
    CT installation

    Resolution
    PowerLogic™ Split-Core Branch Current Monitor
    BCMSC
    Each current sensor can monitor conductors carrying up to a maximum of 50 amperes. Maximum wire size capacity is #6 
    THHN, 0.4 in. (10 mm) diameter.
     
    PowerLogic™ Branch Current Monitor
    BCM42H (E) and BCM42Y55 (E)
    Each current sensor can monitor conductors carrying up to a maximum of 100 amperes. Maximum wire size capacity is 
    #4 THHN, 0.4 in. (10.16 mm) diameter.