    What causes a flashing P on the ATV21 and ATV212 drives?

    Issue:
    What causes a flashing P on the ATV21 and ATV212 drives?

    Product Line:
    Altivar ATV21, ATV212

    Environment:
    All

    Cause:
    Pre-Alarm P

    Resolution:
    The flashing P means the DC bus is in pre alarm or the drive controller is approaching an overvoltage fault due to a high supply line, regenerative motor braking or power disturbance.
    Press MODE button until you see AUF, arrow down to F---, press ENT to the extended menu F codes.
    F626 you can change the overvoltage threshold setting to 150%.
    F305 you can disable the overvoltage or change when the drive protects against overvoltage.