    Do the Advantys STB Power distribution modules (PDT) require an Input Power connection (Sensor Bus) for the island to function properly ?

    Title

    Input power required on a PDT module.

    Issue

     

    Product Line

    Advantys STB

    Environment

     

    Cause

     

    Resolution

    With the 24 Vdc Power distribution module (STBPDT3100), you are required to have this connection, otherwise you will receive a module error (Flashing ERR led) on all 24 Vdc input modules. With the 115/230 Vac Power distribution module (STBPDT2100), you are not required to have this connection, therefore allowing you to connect directly from the field device to the input module.